SD

Permissible as single fastening. Permissible load in cracked and non-cracked normal concrete of strength ≥ C20/25. Manufacturer’s information has to be observed strictly (ETA-05/0069).

galvanized, according to ISO 4042
АртикулProduct
Lmin
Minimum drilling depth
diameterdiameter
t
material thickness
Pzul
permissible tractive force
PzulR30
permissible tensile load under the influence of fire (30min)
PzulR90
permissible tensile load under the influence of fire (90min)
weight
SDK 10/1055 mm10 mm10 mm0-10 mm4.30 kN1.80 kN1.80 kN5.88 kg/100
SD 8/1055 mm8 mm8 mm0-10 mm3.60 kN1.40 kN0.90 kN3.50 kg/100
SD 8/3055 mm8 mm8 mm0-30 mm3.60 kN1.40 kN0.90 kN4.40 kg/100
SD 10/1075 mm10 mm10 mm0-10 mm5.70 kN2.80 kN1.90 kN6.20 kg/100
SD 10/3075 mm10 mm10 mm0-30 mm5.70 kN2.80 kN1.90 kN7.80 kg/100
SD 12/1090 mm12 mm12 mm0-10 mm9.50 kN5.00 kN3.20 kN11 kg/100
SD 16/25110 mm16 mm16 mm0-25 mm13.40 kN9.40 kN6.00 kN26.30 kg/100
Stainless steel, according to ASTM 31 Ti / AISI 316 L, BS 320S17 / BS 316S11
АртикулProduct
Lmin
Minimum drilling depth
diameterdiameter
t
material thickness
Pzul
permissible tractive force
PzulR30
permissible tensile load under the influence of fire (30min)
PzulR90
permissible tensile load under the influence of fire (90min)
weight
SD 8/10E455 mm8 mm8 mm0-10 mm3.60 kN1.40 kN0.90 kN3.60 kg/100
SD 10/10E475 mm10 mm10 mm0-10 mm5.70 kN2.80 kN1.90 kN6.20 kg/100
SD 10/30E475 mm10 mm10 mm0-30 mm5.70 kN2.80 kN1.90 kN7.10 kg/100
SD 12/10E490 mm12 mm12 mm0-10 mm9.50 kN5.00 kN3.20 kN10.90 kg/100